Recall on Detroit Generators from Total Tools

Published: 10 February 2014 Category: Industry News

The 7.5KVA 15HP Recoil Start Generator & the 3.1KVA 2500W 6.5HP Recoil Start Generator has been recalled as it was manufactured with a Multiple Earth Neutral (MEN) link between the live & earth without a Residual Current Device (RCD), which is non-compliant with safety clause 6 of AS2970 Electricity generating sets.

Recall on Detroit Generators from Total Tools

Product description

A.) 7.5KVA 15HP Recoil Start Generator

B.) 3.1KVA 2500W 6.5HP Recoil Start Generator

Identifying features

A.) Part # YW8000HECO

B.) Part # DFD3000HS2

What are the defects?

Manufactured with a Multiple Earth Neutral (MEN) link between the live & earth without a Residual Current Device (RCD), which is non-compliant with safety clause 6 of AS2970 Electricity generating sets.

What are the hazards?

If a fault occurs in the unit or equipment the MEN, which is bonded to the frame, can cause the frame to become live with electrical current possibly causing an electric shock.

Where the product was sold

  • Australian Capital Territory
  • New South Wales
  • Queensland
  • South Australia
  • Victoria

Traders who sold this product

37 Total Tools franchised stores

Supplier

Total Tools

Supplier's web site

http://www.totaltools.com.au/

What should consumers do?

Consumers should bring their unit to a Total Tools store to get the product remedied.


Source: http://www.recalls.gov.au/content/index.phtml/itemId/1055776